IEXCB451232AV

Features

Technology
Basic
Energy Metering
No
Metering per Input Line
No
Metering per Output Receptacle
No
Remote Outlet Switching
No
Ethernet Port
No
Networking Protocols
No
PDU Cascading
No
Power Share
No
Display
No
Residual Current Monitoring
No
USB Ports
No
Environmental Sensors
No

Input

Plug
IEC 60309 1P+N+E 6h 32A 250V SINGLE PHASE
Lead Length
3 meter
Cable Type
H07RN-F3G4.0 mm²
Max. Input Load
16A
Rated Input Voltage
190-250V Single phase
Frequency
50-60Hz
Power Capacity
7360W

Output

Rated Output Voltage
190-250V Single phase
Output Types
12 IEX (C13/C19) combo (Max rate 16A) EN61984+UL498 certified
Overload Protection
(2) 1 Pole Carling 16A L Series L31-B0-24-616-H12-D3

Chassis

Dimensions (W x D x H)
682 x 55 x 55.4 mm
Color
RAL 9004 black powder coat
Mounting Options
4 mounting options (see page 2)
Required Torque for Mounting Screws
≥2.54N·m (25.9kgf-cm or 22.4 in-lbs)

Operating Environment

Temperature Range
0º to 60º C (30º to 140º F)
Humidity
0 - 95 %
Eleva
0 - 4000 Meters
CONFORMANCE
IEC 62368-1 (Third Edition)

Product feature

Feature 1
Feature 2
Feature 3
Feature 4

Build-to-Order

A build-to-order system that enables us to produce client-specific products not dependent on quantity within just a few weeks. The backbone of our business ensures total control of all processes, from quote to invoice.